SYNC-MODB Rev AThis manual must only be used by aqualified heating installer / servicetechnician. Read all instructions,including this manual, theInst
104 Wiring RequirementsFigure 4-2_Control InputsGAS PRESSURE SWITCHROOM THERMOSTAT /ZONE CONTROLFLOW SWITCHSYSTEM SENSOROUTDOOR SENSORSEQUENCER / BUI
114 Wiring Requirements (continued)Figure 4-3_Control OutputsLOW VOLTAGE CONNECTIONBOARDPRIMARYCONTROL MODULEALARM BELLRUN TIME CONTACTSSEQUENCER / B
124 Wiring RequirementsFigure 4-4_Control LocationCONTROLLER 1CONTROLLER 2MODBUS COMMUNICATIONBOARD (MTR01)HEAT EXCHANGER 1HEAT EXCHANGER 2Modbus Ins
134 Wiring Requirements (continued) Modbus RS485 Communication Bus Modbus RS485 Port on Gateway or Building System Physical Configuration: Direct Co
145 Unit OperationUnit Operation with Modbus CommunicationsTo control a SYNC boiler through a Building Management System communicating through Modbus
155 Unit Operation (continued)Demand Configuration 6In this configuration the unit is controlled by setting the modulation setpoint from 0 - 100%.Rat
165 Unit OperationCascadeIn order to operate the SYNC boiler in Cascade with Modbuscommunications, configure the leader boiler per the demandconfigur
17TemperatureThe SYNC boiler passes temperature data in degrees Celsius.Also, to accommodate decimal places the decimal value must bedivided by 10.Her
186 Troubleshooting Should you encounter problems communicating overModbus, the following items should be checked in this order:1. Physical Layer2. C
196 Troubleshooting (continued)Lockout Codes (Input Registers 30016 and 30025)161 = EEPROM code Parameters not Re-Programmed by Lochinvar164 = EEPROM
21 IntroductionThe information contained in this manual provides general guidelines for the implementation of Modbus communication withthe Lochinvar
20Modbus InstructionsBOX DEPICTSOPTIONAL ITEMSLADDER DIAGRAMLBL20058 REV ECONTROLMODULE 2X5-3X2-1GAS VALVEGAS VALVERELAYX5-5X5-13X5-6X5-121245TR1X1-7F
21Modbus Instructions7 Diagrams (continued)Figure 7-2 Ladder Diagram_Part 2BOX DEPICTSOPTIONAL ITEMS120 VAC24 VAC120VACTERMINAL STRIP120V SUPPLY &quo
22Modbus Instructions7 DiagramsFigure 7-3 Wiring DiagramBOX DEPICTSOPTIONAL ITEMSOUTLETSENSORNotes:1. All wiring must be installed in accordance wit
23Notes
Revision Notes: Revision A (ECO #C04560) initial release.SYNC-MODB Rev A 10/09
32 ConfigurationAddressingThe Modbus addressing space is comprised of 256 differentaddresss.• 0 is reserved for broadcast messages from the master de
4Modbus Instructions2 ConfigurationTiming SpecificationsThe baud rate for the Modbus board is selectable with Dipswitch #9.1 = 19200 bps0 = 9600 bpsE
52 Configuration (continued)Modbus InstructionsFunction Sub FunctionHEX DescriptionDec HEX Dec1 01 Read Coil Status2 02 Read Input Status3 03 Read Ho
6Modbus Instructions2 Configuration MODBUS Exception CodesCode Name Meaning01 ILLEGAL FUNCTIONThe function code received in the query is not an allow
7Modbus InstructionsPrimary Data TablesTable Data Type Read / WriteDiscrete Inputs Single Bit Read OnlyCoils Single Bit Read / WriteInput Registers 16
8Modbus InstructionsInput RegistersAddress Description Default Unit Min. Max. Resolution30001 Discrete Inputs 1 - 16 0 NA 0 65535 130002 Discrete Inpu
9Modbus Instructions4 Wiring RequirementsRS-485 Communication Bus• Maximum Length = 4000 feet• Cable Specification = 24 AWG / A,B (twisted pair) and