INSTALLATION AND SERVICE MANUAL
Save this manual for future reference.
WWAARRNNIINNGG
: If the
information in this manual
is not followed exactly, a
fire or explosion may
result causing property
damage, personal injury or
loss of life.
– This appliance MUST
NOT be installed in any
location where gasoline or
flammable vapors are
likely to be present, unless
the installation is such to
eliminate the probable
ignition of gasoline or
flammable vapors.
WHAT TO DO IF YOU SMELL
GAS
Do not try to light any
appliance.
Do not touch any
electric switch; do not
use any phone in your
building.
Immediately call your
gas supplier from a
neighbors phone.
Follow the gas
suppliers instructions.
If you cannot reach your
gas supplier, call the fire
department.
– Installation and service
must be performed by a
qualified installer, service
agency or the gas supplier.
WWAARRNNIINNGG
: Do not use
this pool heater if any part
has been under water. The
possible damage to a
flooded pool heater can be
extensive and present
numerous safety hazards.
Any pool heater that has
been under water must be
replaced.
GAS HEATERS FOR COMMERCIAL
POOL APPLICATIONS
500,000 - 2,070,000 Btu/hr MODELS
Starting Serial #F0600187510
CPE-i&s-05
WWAARRNNIINNGG
: Improper
installation, adjustment,
alteration, service or
maintenance can cause
property damage, personal
injury, exposure to
hazardous materials or
loss of life. Refer to this
manual. Installation and
service must be performed
by a qualified installer,
service agency or the gas
supplier. This pool heater
contains materials that
have been identified as
carcinogenic, or possibly
carcinogenic, to humans.
Vue de la page 0
1 2 3 4 5 6 ... 59 60

Résumé du contenu

Page 1 - Starting Serial #F0600187510

INSTALLATION AND SERVICE MANUALSave this manual for future reference.WWAARRNNIINNGG: If theinformation in this manualis not followed exactly, afire o

Page 2

IINNSSTTAALLLLAATTIIOONN ContinuedVVEENNTTIINNGGGeneral InformationYou must supply adequate combustion and ventilation air tothis pool heater. You mu

Page 3 - IINNFFOORRMMAATTIIOONN

Figure 12 – Vent Termination from Flat Roof 10' or Lessfrom Parapet WallFigure 13 – Vent Termination from Flat Roof More Than 10'from Parape

Page 4

IINNSSTTAALLLLAATTIIOONN ContinuedCombustion Air Inlet Piping WARNING: Locate and install thecombustion air inlet cap correctly. Failure to doso can

Page 5 - IIDDEENNTTIIFFIICCAATTIIOONN

Figure 14 – Sidewall Combustion Air InletFigure 15 – Air Inlet Cap for Sidewall TerminationTo prevent recirculation of flue products from an adjacent

Page 6

IINNSSTTAALLLLAATTIIOONN Continuedto the common air inlet. This exterior opening for combustionair must connect directly to the outdoors. The total l

Page 7 - COMBUSTION AND VENTILATION

Connect the flue vent directly to the flue outlet opening on thetop of the pool heater. No additional draft diverter orbarometric damper is needed on

Page 8

IINNSSTTAALLLLAATTIIOONN Continuedproblems. The temperature of the flue products from a highefficiency pool heater may not be able to sufficiently he

Page 9 - Exhaust Fans

Figure 20 – Vertical DirectAire Installation with RooftopCombustion Air InletVent Kits WARNING: Only use a sidewall air inlet capsupplied by the appl

Page 10 - Commercial Pool Heaters

IINNSSTTAALLLLAATTIIOONN ContinuedSidewall FanThe sidewall fan can be mounted on the inside/outside(depending upon model) with a sidewall vent hood i

Page 11 - Flue and Air Inlet Pipe Sizes

Figure 22A – Direct Vent (Illustration with Sidewall Ventand Sidewall Combustion Air)Figure 22B – Sidewall Venting WARNING: Do not combine the flue f

Page 12

Commercial Pool Heaters2TTaabbllee ooff CCoonntteennttssGeneral Product Information . . . . . . . . . . . . . . . . . . . . . . . . .3Special Instr

Page 13 - Combined Air Inlet Points

IINNSSTTAALLLLAATTIIOONN Continued Input Kit* Max. Vent Vent Max. VentBtu/hr (w/Power Length Termination Only LengthFan Assy.)(500,0

Page 14

For proper operation, a barometric damper is provided forHorizontal DirectAireTMinstallations. The damper will help toensure a draft between negative

Page 15 - Flue Outlet Piping

IINNSSTTAALLLLAATTIIOONN Continued90° elbow. Subtract 2.5 feet (0.7m) of equivalent length for each45° elbow.Masonry Chimney InstallationDo not use a

Page 16

In cold climates, use a Type-B doublewall vent pipe or aninsulated single wall pipe for combustion air. This will helpprevent moisture in the cool inc

Page 17 - 3. Sidewall Venting

IINNSSTTAALLLLAATTIIOONN Continued2. On horizontal runs, do not install vent pipe with seamspointing down. Position vent pipe so that the seams are o

Page 18

Vertical Combustion Air Inlet ClearancesYou must locate the air inlet termination elbow at least 12"(30cm) above the roof or above normal snow le

Page 19

IINNSSTTAALLLLAATTIIOONN Continued* These kits include an outdoor vent cap and gasket.Flue gas condensate can freeze on exterior walls or on the vent

Page 20

2. Isolate the pool heater from the gas supply piping systemby closing a manual shutoff valve during any pipingsystem pressure testing that is equal

Page 21 - 5. Direct Venting

IINNSSTTAALLLLAATTIIOONN ContinuedFigure 29 shows a typical pool heater gas train.Figure 29 – Typical Pool Heater Gas Train DrawingCombination Gas Va

Page 22

13. Remove the manometer and related fitting from the “inlet”side of the gas valve, replace 1/8" hex plug in the gas valveand tighten.14. Turn on

Page 23

GGEENNEERRAALL PPRROODDUUCCTTIINNFFOORRMMAATTIIOONNSpecial InstructionsThis manual supplies information for the installation,operation and servicing

Page 24

IINNSSTTAALLLLAATTIIOONN ContinuedGas Manifold Pressure AdjustmentIMPORTANT: The gas valves are referenced tothe fan pressurized chamber by a hosecon

Page 25 - Outdoor Vent Cap Kit

* Net Manifold Pressure equals the measured manifold pressure minus the chamberpressure. See Figure 31 to measure the Net Manifold Pressure.POOL HEATE

Page 26

IINNSSTTAALLLLAATTIIOONN ContinuedNote: If the wing nut underneath the valve actuator body isloose, retighten.9. Reinstall the plastic actuator cover

Page 27 - Gas Train and Controls

Installation and Service Manual33Figure 34 - Heater is Within 15 Feet of Pool PipingFigure 35 - Heater is Beyond 15 Feet of Pool Piping

Page 28

Commercial Pool Heaters34Figure 36 - Heaters are within 15 feet Perpendicular of Pool PipingFigure 37 - Heaters are Beyond 15 feet of Pool PipingIINNS

Page 29

Installation and Service Manual35Relief ValveThis pool heater is supplied with a relief valve(s) sized inaccordance with ASME Boiler and Pressure Vess

Page 30

Commercial Pool Heaters36IINNSSTTAALLLLAATTIIOONN ContinuedEnsure that the pump installed on the pool heater will supplyadequate flow to make the flo

Page 31 - INSTALLATION

Installation and Service Manual37Figure 39 - Control Panel Component Location DrawingTABLE–NTerminal Strip Connection OptionsThe scenarios shown in Fi

Page 32

Commercial Pool Heaters38IINNSSTTAALLLLAATTIIOONN ContinuedFigure 40 (A-C) - Terminal Strip ConnectionOPERATIONFOR YOUR SAFETY READ BEFOREOPERATING

Page 33

39Figure 42 – ON/OFF Switch8. Turn the manual gas cock clockwise  to the “OFF”position.9. Wait five (5) minutes to clear out any gas. If you smell

Page 34

• do not try to light any appliance• do not touch any electrical switch; do not use any phone in your building• immediately call your gas supplier fro

Page 35 - Water Flow Switch

Commercial Pool Heaters40OPERATIONContinuedFigure 44 – Vertical Pool Heater PipingFigure 45 – Horizontal Pool Heater PipingOPERATING TEMPERATURE CONTR

Page 36

Installation and Service Manual41pool return sensor has been installed and connected, this willbe the temperature of the water coming from the pool.By

Page 37 - Gauge Allowable Length

Commercial Pool Heaters42OPERATIONContinuedHOT SURFACE IGNITION SYSTEMHot Surface Igniter and Ignition ControlModuleThis unit has one ignition module

Page 38

Installation and Service Manual43Access to Internal Control Panel The control panel is accessed by turning the knurled knoblocated at the bottom cente

Page 39

Commercial Pool Heaters44OPERATIONContinuedOPERATION AND DIAGNOSTICINDICATORSThe control panel has up to six indicating and diagnostic lightsto show a

Page 40

Installation and Service Manual45Chlorine residual is the chlorine remaining in the pool waterafter it is consumed in the process of destroying bacter

Page 41 - Temperature Controller

Commercial Pool Heaters46OPERATIONContinuedPipe Size RequirementsThe pipe sizing chart provides the minimum pipe size forcommon manifold piping to ens

Page 42

Installation and Service Manual47High Water Temperature Limit ControlThis pool heater is equipped with a fixed setting, auto resethigh water temperatu

Page 43 - Code Sequence Condition

Commercial Pool Heaters48CLEANING ANDMAINTENANCE ContinuedBurner Removal and Cleaning1. Turn “OFF” the main power to the pool heater.2. Turn “OFF” th

Page 44

Installation and Service Manual49Combustion Air FansBoth the 500,000 - 750,000 Btu/hr models and the 990,000 -2,070,000 Btu/hr models use a fan-assist

Page 45

PPRROODDUUCCTTIIDDEENNTTIIFFIICCAATTIIOONNInstallation and Service Manual5Figure 1B - Optional Vertical Piping LoopFigure 1A - Standard Horizontal Pip

Page 46

Commercial Pool Heaters50CLEANING ANDMAINTENANCE ContinuedIf the air pressure switch does not make within 60 secondsfrom the time the fans turn ON, th

Page 47 - MAINTENANCE

Installation and Service Manual51ENERGY SAVINGRECOMMENDATIONS 1. Keep the pool covered when not in use. This will cutheating cost, reduce water evapo

Page 48

Commercial Pool Heaters52GLOSSARYPOWER SUPPLY120VAC/60Hz/1PH power connects to black (line) and white(neutral) wires located within an electrical wiri

Page 49 - LESS AIR

Installation and Service Manual53PREPURGE(Ignition Module Function)Once the ignition module sees a 24VAC input from its pressureswitch, it runs the bl

Page 50

Commercial Pool Heaters54WIRING BOX CONNECTIONS

Page 51 - SEQUENCE OF OPERATION

Installation and Service Manual55WIRING BOX CONNECTIONS

Page 52

Commercial Pool Heaters56 LADDER DIAGRAM

Page 53

Installation and Service Manual57 CONTROL BOX CONNECTIONS

Page 54

Unit Start Up ChecklistEnsure that the location and installation of the equipment is inaccordance with the installation manual, all local installation

Page 55

Advanced settings:By pressing the Select key in the View mode while viewing theBoiler ΔT reading (or the Supply Sensor temperature if thePool Supply

Page 56

INSTALLATIONThis pool heater meets the safe lighting performance criteriawith the gas manifold and control assembly provided, asspecified in the ANSI

Page 57

6/06-Printed in U.S.A.Lochinvar Corporation • 300 Maddox Simpson Pkwy • Lebanon, TN 37090 • 615-889-8900 / Fax 615-547-1000www.Lochinvar.com

Page 58 - Appendix A

FREEZE PROTECTIONAlthough this pool heater is CSA design certified for outdoorinstallations - such installations are not recommended in areaswhere the

Page 59 - Appendix B

IINNSSTTAALLLLAATTIIOONN Continued CAUTION: Some pleated filters are toorestrictive and could cause air flow problems.For convenience and flexibilit

Page 60 - 6/06-Printed in U.S.A

Figure 7 – Outside Combustion Air - Two Openings2. Outside Combustion Air, Using DuctsYou can direct outside combustion air to this pool heater usingt